Solar thermography: what a drone thermal inspection can and cannot find

MethodUnited StatesUpdated

A thermal camera finds heat. It does not find defects. Everything that makes an infrared survey worth paying for happens in the gap between those two sentences: the conditions you fly in, the file format you keep, and knowing which four defect types will never appear in the imagery at all.

The weather decides the result before you take off

A defective solar cell does not glow on its own. It heats up because current is being forced through a resistance, and current only flows when the sun is on the module. Fly on a weak day and the fault has no energy to reveal itself with. This is the single most common reason a thermal survey comes back clean on an array that is losing money.

IEC TS 62446-3:2017 is the technical specification for outdoor infrared thermography of PV systems, and it puts numbers on this. Two of them do most of the work.

600

W/m² minimum, in the plane of the module

Not ambient, not horizontal. Measured in the module's own plane, which on a tracker moves through the day. Below this, the standard considers a module inspection invalid.

3 cm

Maximum module edge per pixel

The standard specifies ground resolution, not sensor size. Hit 3 cm per pixel and a 640 by 512 camera works at a sensible altitude. A 320 by 256 camera has to fly roughly half as high, which doubles the flight lines.

3

Conditions nobody checks

Irradiance gets measured. Wind, cloud cover and the sun's own reflection off the glass are the three that quietly ruin files which looked fine on the controller screen.

Both figures are from IEC TS 62446-3, Edition 1.0, 2017-06. Secondary engineering guidance commonly adds a wind limit around 4 on the Beaufort scale and a cloud limit around 2 okta of cumulus. We have not verified those two against the standard text, so treat them as working practice rather than as requirements.

Radiometric, or you have a picture of a problem

This is where most inspection money is wasted, and it is entirely avoidable. A radiometric thermal file stores a temperature value behind every pixel. Open it six months later and you can still put a cursor on a cell and read 68 degrees. A non-radiometric file stores colour only. The temperatures were used to pick the colours and then thrown away, and nothing recovers them.

An orange blob on a blue panel is not a measurement. It is a screenshot of one. When a module manufacturer is deciding whether to honour a warranty, or an adjuster is deciding whether hail caused the damage, the difference between those two files is the difference between a claim and a conversation.

What you are handedHolds temperaturesGood forUseless for
Radiometric JPEG (R-JPEG) or TIFFYes, per pixelMeasurement, re-analysis, claims, year-on-year comparisonNothing. Keep these.
Radiometric videoYes, per frameScanning large areas quicklyPrecise per-module values; frame geometry moves
Standard JPEG or PNG of a thermal viewNoShowing someone roughly where to lookAny claim, any temperature value, any re-analysis
PDF report with thermal images embeddedNoReading the contractor's conclusionsChecking them

Put it in the contract. The deliverable is the radiometric originals plus the report, and the originals are yours. A contractor who will not hand over the raw files is selling you their opinion, and you cannot audit an opinion three years later when the modules start failing.

Each heat pattern means something different

A hot module and a hot cell are not the same finding, and they do not go on the same work order. The shape of the heat is what tells you which one you have. The patterns below are the ones that account for most of what a survey returns on an operating site.

What you seeUsual causeWhat it costs youUrgency
One cell hot, neighbours normalCell crack, shading, local contamination, or a manufacturing defectSmall now. A hot cell is a wear process, not a steady stateMonitor, re-fly next cycle
A block of cells hot, bounded by the substringBypass diode conducting, usually a failed diode or a shaded substringRoughly a third of the module's output while it conductsWork order
Whole module uniformly warmer than its rowSeries resistance, connector degradation, or interconnect fatigueModest per module, and it tends to spread along the stringWork order
Whole string or row flat and coolOpen circuit upstream: connector, fuse, combiner or inverter inputThe entire string. This is the expensive oneSame day
Junction box hot, module otherwise fineLoose or corroded termination inside the boxSmall output loss, real fire riskSame day, safety item
Gradient across many modules, worse near the framePotential induced degradation, early stageCreeping, portfolio-wide, easy to misread as normal variationInvestigate with electrical test
Patchy warm areas with soft edgesSoiling, bird droppings, vegetation shadowRecoverable by cleaning, not a defect at allCleaning schedule

Temperature-difference thresholds for grading these into severity classes circulate widely in vendor material. The figures we have seen are presented by their own authors as indicative engineering guidance rather than normative text, so we have not reproduced them here as rules. If a contractor grades your anomalies by a numeric threshold, ask which document it comes from.

Four things thermography will not show you

Every vendor page covers detection. Almost none covers the gaps, which is a problem when the gaps are what gets an asset owner into trouble. A clean thermal report is not a clean array. It is a clean array as far as one method can see, and the method has known blind spots.

Microcracks, until they are already costing you

A crack in a cell is invisible to infrared until it becomes electrically active and starts producing heat. That delay can be years. Electroluminescence imaging sees cracks directly, but it needs darkness and an injected current, so it is a night-time ground operation, not a drone flight. After a hail event, a clean thermal survey tells you nothing about crack load.

Potential induced degradation, early on

PID appears in thermal imagery eventually, as a gradient worst near the grounded frame. By then it has usually been progressing for a while. Catching it early needs electrical measurement on the string, not imagery.

How much power you are actually losing

Thermography locates and classifies. Turning that into kilowatt-hours needs the module datasheet, the string topology and production data for the same period. Any yield-loss figure quoted from thermal imagery alone is a model output, and you should be able to see the model.

Cause, as opposed to symptom

Heat tells you where the energy is going, not why. A hot connector and a hot cell can both read as a warm module. The second site visit, with a meter, is what separates them, and it is the step that gets cut from cheap quotes.

What we do not do

We do not fly these inspections. This site documents how the work is specified, bought and closed out in the United States. The imagery in our videos is licensed stock, and where a shot looks thermal it is a false-colour treatment of a visible-light clip, stated as such every time.

Where this goes next

The anomaly list is not the deliverable. A module address, a severity, an owner and a re-flight date is the deliverable. That handoff is the seven-step workflow, and step five, the re-flight that verifies the repair, is the one most programmes skip.

Six lines to put in the scope

Most disappointing inspections were bought badly rather than flown badly. These are the clauses that decide whether the output is usable, and they cost nothing to ask for before the contract is signed.

  1. Irradiance at capture must be recorded, measured in the plane of the module, and must meet 600 W/m² for every module pass. A survey flown below that gets re-flown at the contractor's cost.
  2. Ground resolution of 3 cm per pixel or better on module passes, with tighter resolution on electrical connections and combiners.
  3. Radiometric originals delivered to you, in a documented format, alongside the report. Not screenshots and not a PDF.
  4. Every anomaly tied to a module address that matches your own asset register, not to a pin on an unreferenced map.
  5. Severity classification with its source document named, so your engineer can check the grading rather than accept it.
  6. A re-flight of repaired zones, scheduled and priced in the original contract. Bought afterwards, it never happens.

If a quote is much cheaper than the others, one of these six is usually what has been removed. Ask which.

Common questions about solar thermography

What irradiance does a solar thermal inspection need?

IEC TS 62446-3:2017 sets a minimum of 600 W/m² measured in the plane of the module for module inspection. Below that, a defective cell does not carry enough current to heat up measurably, so a real fault can read as a clean panel. Most US sites reach 600 W/m² for only a few hours a day, and in winter some do not reach it at all.

What camera resolution is required for PV thermography?

The standard specifies it as ground resolution rather than sensor size: a maximum of 3 cm of the module edge per pixel for module inspection. A 640 by 512 sensor meets that at a normal survey altitude. A 320 by 256 sensor forces the aircraft much lower and multiplies flight time. For electrical connections the standard requires resolution matched to the smallest object being verified, which is tighter.

What is the difference between radiometric and non-radiometric thermal images?

A radiometric file stores a temperature value for every pixel, so any point can be measured after the flight. A non-radiometric file stores only colours, so the temperature information is gone and cannot be recovered. An adjuster or a warranty claim needs measurable temperatures, which makes a non-radiometric export evidence of nothing. Keep the radiometric originals alongside the report.

Can a thermal camera detect microcracks in solar panels?

No. A microcrack only appears in infrared once it has become electrically active and started generating heat, which can be months or years after it forms. Electroluminescence imaging detects cracks directly but needs darkness and a current source, so it is not a drone survey. A clean thermal report does not mean a hail-struck array is undamaged.

Does a thermal inspection tell you how much power you are losing?

Not directly. Thermography locates and classifies anomalies. Converting those into lost kilowatt-hours needs the module datasheet, the string layout and production data for the same period. A vendor who quotes a yield-loss figure from thermal imagery alone has modelled it, and the model should be visible to you.

How often should a solar farm have a thermal inspection?

Annually as a baseline, plus an event-driven flight after any hail, wind or flood event that could have damaged modules. In hail-prone states a pre-season condition flight before the spring peak is worth more than the annual one, because it records the array's state before the damage instead of after it. Our state hail analysis shows where that applies.

Where the figures come from

  • IEC TS 62446-3:2017, Edition 1.0, 2017-06, Photovoltaic (PV) systems. Requirements for testing, documentation and maintenance. Part 3: Outdoor infrared thermography. Source of the 600 W/m² plane-of-module minimum and the 3 cm per pixel ground resolution limit. Preview pages.
  • IEA PVPS Task 13, Review on Infrared and Electroluminescence Imaging for PV Field Applications. Background on what infrared imaging detects and where electroluminescence is required instead.
  • Wind, cloud-cover and temperature-difference figures in circulation are from secondary engineering guidance whose own authors describe them as indicative rather than normative. They are flagged as unverified wherever they appear above.

Checked 9 November 2026. Reference material, not engineering, insurance or legal advice. No personal data is collected on this site.